Part P/ BS 7671 / 16th Edition
7
Professional Insulation TesterIN2103
Insulation Tests:
250V: 4/40/400/1000MΩ
500V: 4/40/400/4000MΩ
1000V: 4/40/400/5000MΩ
Range: 0.200MΩ to 5000MΩ
Short Circuit Current: <1.5mA
Accuracy: ± (3% rdgs + 5 digits)
Auto-Discharge: Yes
Buzzer disable option: Yes
Continuity:
Range: 0.01Ω to 40.00Ω
Resolution: 0.01Ω
Short Circuit Current: >200mA
Accuracy: ± (3% rdgs + 5 digits)
Auto-Discharge: Yes
Buzzer: <30Ω
Resistance:
Range: 0.1Ω - 1999kΩ
Open Voltage: 3V
Accuracy: ± (3% rdgs + 5 digits)
Voltage Test:
Voltage Range: 600V AC/DC,
Voltage Warning Indicator: >30V
Accuracy: ± (3% rdgs + 5 digits)
Digital Display: 4000 count
Analogue Bargraph: 51 segment
Batteries: 6 x 1.5V AA Alkaline
User settable Limits, Pass/Fail
Indicators, Polarisation Index,
Dielectric Absorption Ratio, APO
disable option, Memory, Backlight,
Autohold, Auto Zero
Protection: IP44
Overvoltage: 600V CAT III
Complies with: BS EN 61010, BS
EN 61557 & BS 7671:2001
(16th Edition)
Optional fused test leads: TL57
Replacement test leads: TL47
Dimensions: 90 x 210 x 54mm
Includes: batteries, manual, carry
case & test leads (TL47)
The top of the range IN2103 insulation and continuity tester offers 250, 500 and 1000V
tests. As with all models in this range, a large clear backlit digital display and analogue
bargraph shows the test voltage as well as the insulation reading.
In addition to all the features of the IN2101 and IN2102, the IN2103 has user settable
limits with PASS/FAIL indication and a memory to store and compare readings.
This advanced tester also includes both Polarisation Index (PI) and Dielectric
Absorption Ratio (DAR) measurements. These sophisticated tests, introduced for the
first time in a handheld instrument, allow for more accurate measurement of insulation
values.
This range also incorporate an internal battery check facility, which indicates the energy
levels as both a percentage and a voltage.
They also fully comply with the Part P building regulations inspection and testing
requirements, as well as all the relevant standards.
MARIN2103 insulation tester £328.70
TC2A calibration £27.00
MARTL57 optional fused test leads £32.40